Product Hierarchy
Product Hierarchy

IOP6AU - Category 6A Indoor/Outdoor Cable, 4 Pair, U/UTP, CMP/CMX, Gel Free


Category 6A Premise Horizontal Cable, Indoor/Outdoor, 4 Pair, 23 AWG Solid Bare Copper Conductors, U/UTP, Plenum-CMP/CMX Outdoor, Gel Free

Product Overview

Suitable Applications: Indoor/Outdoor, Premise Horizontal Cable, Ethernet up to 10GBASE-T, Wi-Fi 6, Wi-Fi 5, PoE++, PoE+, PoE, Noisy Enivronments, HDBaseT, IP Cameras, Wet Locations following Product Notes
Patent: This product has one or more applicable patents. More information on patents can be found at https://www.belden.com/patents.

Construction Details

Conductor
SizeStrandingMaterialNo. of Pairs
23SolidBC - Bare Copper4
Insulation
MaterialColor Code
FEP - Fluorinated Ethylene PropyleneWhite & Blue, White & Orange, White & Green, White & Brown
Outer Jacket
SeparatorMaterialNom. DiameterRipcord
Center Member (Patented X-Spline®), EquiBlock™ Barrier TechnologyPVDF - Polyvinylidene Fluoride0.27 in (6.9 mm)Yes
Overall Cable Diameter (Nominal): 0.27 in (6.9 mm)

Electrical Characteristics

Electricals
Max. Conductor DCRMax. Capacitance Unbalance
82 Ohm/km (25 Ohm/1000ft)45 pF/100m
Delay
FrequencyMax. DelayMax. Delay SkewNom. Velocity of Prop.
100 MHz537.6 ns/100m45 ns/100m70%
High Frequency
Frequency [MHz]Max. Insertion Loss (Attenuation) [dB/100m]Min. NEXT [dB]Min. PSNEXT [dB]Min. ACR [dB]Min. PSACR [dB]Min. ACRF (ELFEXT) [dB]Min. PSACRF (PSELFEXT) [dB]Min. RL (Return Loss) [dB]Max./Min. Input Impedance (unFitted)Max./Min. Fitted ImpedanceMin. PSANEXT [dB]Min. PSAACRF [dB]Min. TCL [dB]Min. ELTCTL [dB]
12.174.372.372.270.267.864.820.0105 +/- 10115 +/- 1567.067.040.035.0
43.865.363.361.559.555.852.823.0105 +/- 10100 +/- 767.066.240.023.0
85.360.858.855.453.449.746.724.5100 +/- 22100 +/- 767.060.140.016.9
105.959.357.353.451.447.844.825.0100 +/- 22100 +/- 767.058.240.015.0
167.556.254.248.846.843.740.725.0100 +/- 22100 +/- 767.054.138.010.9
208.454.852.846.444.441.838.825.0100 +/- 22100 +/- 767.052.237.09.0
259.453.351.344.042.039.836.824.3100 +/- 22100 +/- 767.050.236.07.0
31.2510.551.949.941.439.437.934.923.6100 +/- 22100 +/- 767.048.335.15.1
62.515.047.445.432.430.431.928.921.5100 +/- 22100 +/- 765.642.332.0
10019.144.342.325.223.227.824.820.1100 +/- 22100 +/- 762.538.230.0
20027.639.837.812.210.221.818.818.0100 +/- 22100 +/- 758.032.227.0
25031.138.336.37.35.319.816.817.3100 +/- 32100 +/- 756.530.226.0
30034.337.135.12.90.918.315.316.8100 +/- 32100 +/- 755.328.725.2
35037.236.134.116.913.916.3100 +/- 32100 +/- 754.327.324.6
40040.135.333.315.812.815.9100 +/- 32100 +/- 753.526.224.0
45042.734.532.514.711.715.5100 +/- 32100 +/- 752.725.123.5
50045.333.831.813.810.815.2100 +/- 32100 +/- 752.024.223.0
Voltage
UL Voltage Rating
300 V (CMP), 300 V (CL3P)

Mechanical Characteristics

Temperature
UL TemperatureOperatingInstallationStorage
150C-40°C To +75°C0°C To +60°C-40°C To +75°C
Bend Radius
Installation Min.
2.7 in (69 mm)
Max. Pull Tension: 25 lbs (11 kg)
Bulk Cable Weight: 39 lbs/1000ft (58 kg/km)

Standards and Compliance

Environmental Suitability: Indoor/Outdoor, Water Exposure/Below-Grade Conduit, Indoor, Outdoor, Sunlight Resistance
Flammability / Reaction to Fire: NFPA 262, UL 910 (Plenum), FT6
NEC / UL Compliance: Article 800, CMP
IEEE Compliance: IEEE 802.3bt Type 1, Type 2, Type 3, Type 4
Data Category: Category 6A
TIA/EIA Compliance: ANSI/TIA-568.2-D Category 6A
ISO/IEC Compliance: 11801 ed 2.2 (2011) Class EA
CENELEC Compliance: Segregation class according EN50174-2 = a
European Directive Compliance: REACH

Product Notes

Notes: Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. Print Includes Descending Footage/Meter Markings from Max. Put-Up Length to 0. Not Suitable for Direct Burial. Cable jacket system is specially designed to protect cable core. Cable contains no water-blocking tapes, gels, or powders. Install in accordance with all applicable electrical codes. Maintain jacket integrity throughout installation process. Do not allow water or fluids to penetrate jacket sheath or to enter ends of cable. Ensure ends of cable will be protected from water/fluids after installation.

History

Update and Revision: Revision Number: 0.44 Revision Date: 04-29-2024

Part Numbers

Variants
Item #ColorPutup TypeLength
IOP6AU 0101000BlackReel1,000 ft
Date: 2016-03-02
No accessories are available for this product