Product Hierarchy
Product Hierarchy

3049AE - Inst, 8 TR #16 Str BC, PVC-Nylon Ins E1, OS/IS, Blk PVC Jkt, 300V PLTC-ER CMG




UL Instrumentation, 8 Triad 16AWG (7x24) Bare Copper, PVC-Nylon Insulation E1 Color Code,Indvidual & Overall Beldfoil® Shield, Black PVC Outer Jacket, PLTC-ER CMG AWM 2464 SUN RES DIR BUR

Product Overview

Suitable Applications: Exposed Runs, Hazardous Locations,PLC,4-20ma

Physical Characteristics (Overall)

Conductor
ElementAWGStrandingMaterialNo. of Pairs
Triad(s)167x24BC - Bare Copper8
Comm Wire(s)BC - Bare Copper
Conductor Count: 8
Insulation
ElementMaterialNominal DiameterNominal Wall Thickness
Pair(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.091 in0.017 in
Comm Wire(s)PVC - Polyvinyl Chloride0.066 in
Color Chart
NumberColor
1Black & White and RED 1
2Black & White and RED 2
3Black & White and RED 3
4Black & White and RED 4
Black & White and RED 5
Black & White and RED 6
Black & White and RED 7
Black & White and RED 8
Inner Shield
ElementTypeMaterialMaterial Trade NameDrainwire MaterialDrainwire AWG
TapeBi-Laminate (Alum+Poly)Beldfoil®TC - Tinned Copper18
Comm Wire(s)No Shield
Outer Shield
TypeMaterialMaterial Trade NameDrainwire Material
TapeBi-Laminate (Alum+Poly)Beldfoil®TC - Tinned Copper
Outer Jacket
Nominal DiameterNominal Wall ThicknessRipcord
0.825 in0.050 inYes

Electrical Characteristics

Conductor DCR
Element
Comm Wire(s)
Voltage
DescriptionUL DescriptionVoltage Rating [V]
Type PLTCTC300 V RMS

Temperature Range

Operating Temperature Range: -30°C To +105°C

Standards

NEC/(UL) Compliance: CMG, PLTC-ER, ITC-ER
CEC/C(UL) Compliance: CMG
UL AWM Style Compliance: AWM 2464

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV): Yes
EU Directive 2011/65/EU (RoHS 2): Yes
EU Directive 2012/19/EU (WEEE): Yes
EU Directive 2015/863/EU (RoHS 2 amendment): Yes
EU Directive Compliance: Yes
EU CE Mark: Yes

Suitability

Suitability - Burial: Yes
Suitability - Hazardous Locations: Yes
Suitability - Indoor: Yes
Suitability - Outdoor: Yes
Suitability - Sunlight Resistance: Yes

Flammability, LS0H, Toxicity Testing

UL Flammability: UL 1685 UL Loading

History

Update and Revision: Revision Number: 0.4 Revision Date: 04-28-2026
Instrumentation and Control Cable
Cabling Solutions for Industrial Applications
No accessories are available for this product