29527 - VFD, 3C #2 Str TC XLPE Ins + #10 Symm. Seg. Gnd (3 of #10) Str BC, CTS, Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B


Belden Premium VFD, 2 AWG (7 x 19 x 23) Tinned Copper, 3 Conductor, XLPE Insulation M4 Color Code, With 3 #10 AWG (105 x 30) Bare Copper Drain Wire, Overall Copper Tape Applied Sheild, Black Outer PVC Jacket, 600/1000V TC-ER 90C Dry/Wet 1000V, CSA AWM I/II A/B Sun Res Dir Bur Oil Res II.

Product Overview

Suitable Applications: Variable Frequency Drives (VFD); AC Motor and Drive Systems; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC125A1271RA

Construction Details

Conductor
ElementNo. of ElementsSizeStrandingMaterialNotes
Conductor(s)32 AWG7x19x23TC - Tinned CopperASTM B3 Copper B8 Class B Stranding
Segmented Ground Wire310 AWG105x30TC - Tinned CopperSegmented Ground (3 Totaling 5 AWG)
Insulation
ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.047 in (1.2 mm)0.424 in (10.8 mm)ICEA Chart M4
Ground WireNo Insulation
Outer Shield
Shield TypeMaterialCoverageNotes
TapeBare Copper (BC)100%2 Mil Copper Tape
Bare Copper (BC)
Outer Jacket
MaterialNom. ThicknessNom. DiameterRipcord
PVC - Polyvinyl Chloride0.083 in (2.1 mm)1.090 in (27.69 mm)Yes
Overall Cable Diameter (Nominal): 1.09 in (27.7 mm)

Electrical Characteristics

Electricals
ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Capacitance Cond-to-Other (Conds + Shield)Nom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Conductor(s)0.14 Ohm/1000ft (0.46 Ohm/km)35 pF/ft (110 pF/m)68 pF/ft (220 pF/m)44 Ohm55%130 Amps per Conductor at 30ºC
0.03 Ohm/1000ft (0.098 Ohm/km)
Voltage
UL Voltage Rating
600/1000 V (TC-ER)

Mechanical Characteristics

Temperature
UL TemperatureOperating
90°C Dry, 90°C Wet-20°C To +90°C
Bend Radius
Stationary Min.Installation Min.
10.9 in (277 mm)10.9 in (277 mm)
Max. Pull Tension: 2851 lbs (1293 kg)
Bulk Cable Weight: 969 lbs (440 kg)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
Sustainability: CA Prop 65
Flammability / Reaction to Fire: UL 1685 UL Loading, IEEE 1202 FT4, FT4
NEC / UL Compliance: Article 336, TC-ER, XHHW-2
ICEA Compliance: S-95-658
European Directive Compliance: EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Other Standard Compliance(s): P-07-KA070003-MSHA