Product Hierarchy
Product Hierarchy

127896A - DeviceBus®, 2 Pr #16+18 Str TC, PVC-NYL+PP Ins, IS+OA TC Brd, PVC Jkt, AIA Armor, PVC Jkt, CMG CSA HL

DeviceBus® for ODVA DeviceNet™, 2 Pair 16+18AWG (19x29+19x30) Tinned Copper, PVC-NYL+PP Insulation, Individual Beldfoil® & OA Tinned Copper Braid(65%) Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, CMG CSA HL

Product Overview

Suitable Applications: exposure to rodent, crush, or cut through force, harsh environment, ODVA device-level communication, used with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc.

Construction Details

Conductor
ElementNo. of ElementsSizeStrandingMaterial
Power Pair(s)116 AWG19x29TC - Tinned Copper
Data Pair(s)118 AWG19x30TC - Tinned Copper
Insulation
ElementMaterialNom. ThicknessNom. Insulation DiameterColor CodeNotes
Power Pair(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.022 in (0.56 mm)0.101 in (2.57 mm)Red & Black
Data Pair(s)PP - Polypropylene0.068 in (1.7 mm)0.116 in (2.95 mm)Blue & WhiteFlame Retardant
Inner Shield
ElementShield TypeMaterialCoverage
Power Pair(s)TapeBi-Laminate (Alum+Poly)100%
Data Pair(s)TapeBi-Laminate (Alum+Poly)100%
Outer Shield
Shield TypeMaterialCoverageDrainwire Type
BraidTinned Copper (TC)65%16 AWG (19x29) TC
Inner Jacket
MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.060 in (1.5 mm)0.525 in (13.3 mm)
Armor
Armor Type & Material
AIA - Aluminum Interlock Armor
Outer Jacket
MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.050 in (1.3 mm)0.818 in (20.8 mm)
Overall Cable Diameter (Nominal): 0.818 in (20.8 mm)

Electrical Characteristics

Electricals
ElementNom. Conductor DCRNom. Inner Shield DCRNom. Capacitance Cond-to-CondNom. Characteristic ImpedenceNom. Velocity of Prop.
Power Pair(s)4.9 Ohm/1000ft (16 Ohm/km)1.8 Ohm/1000ft (5.9 Ohm/km)
Data Pair(s)6.9 Ohm/1000ft (23 Ohm/km)14.7 pF/ft (48.2 pF/m)120 Ohm75%
High Frequency
Element
Data Pair(s)
Voltage
Voltage Rating
(300 V)

Mechanical Characteristics

Temperature
UL TemperatureOperating
75°C-40°C to +75°C
Max. Pull Tension: 200 lbs (91 kg)
Bulk Cable Weight: 136 lbs/1000ft (202 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance
Sustainability: CA Prop 65
Flammability / Reaction to Fire: FT4
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.62 Revision Date: 05-31-2024
Date: 2005-04-01
No accessories are available for this product